PHASE FAILURE RELAYS WITH OVER & UNDER VOLTAGE CONTROL, WITH OPTIONAL SEQUENCE, TIME DELAYS

Product

group

D

YWRUPxx, 11WRUPxx, 8WRUPxx (spco), YWR2UPxx (dpco)

Features

  • Din rail mounted
  • Available SPCO or DPCO output
  • Available 3 wire or 4 wire
  • Adjustable over & under voltage control
  • Specify with or without phase sequence
  • Optional adjustable time delay
  • Self powered
  • LED fault indication
  • Transformer technology
Download data sheet

Phase failure relays with independent over and under voltage control, with the option of additional sequence control. Available in either a din rail or 8 & 11 pin plug in housing SPCO with a DPCO option in the din rail housing. All units can be specified as 3 wire or 4 wire. As an option in the din rail housing an adjustable time delay can be specified (not true delay off), which is effective against voltage control, phase sequence (if applicable), but not phase loss or Neutral loss on 4 wire versions (loss of L3 only would produce a time delay). The units are transformers based and thus will ignore transients and harmonic distortions.

The output relay is energised when all three phases are connected and in sequence (if applicable) and within the set voltage limits. The output relay/s will de-energise if one or more voltages between phases are under the value of the minimum set level or above the value of the maximum set level, less any set time delay (if applicable). The units will also de-energise on loss of a phase or incorrect sequence (if applicable). Separate red LED indicators indicate over and under voltage conditions. If both are illuminated this indicates a phase sequence error (if applicable). A green LED indicates output relay status.

Supply & Measuring

Nominal supply:
3 x 110V AC, 3 x 220V AC, 3 x 380V AC,
3 x 400V AC, 3 x 415V AC, 3 x 440V AC

Permanent tolerance: ±15%

System: 3 or 4 wire option

Frequency: 50/60Hz

Umin adjustable: 0-30% of nominal (L - L)

Umax adjustable: 0-20% of nominal (L - L)

Hysteresis: Fixed 3%

Delay on tripping:
Optional 0.1-10sec
Optional 0.2-20sec
Optional 0.3-30sec
Otherwise fixed at 100mSec

Repeat accuracy: +2% of set values

Max power consumption: <3VA

Insulation: 2.5KV 50Hz impulse

Relay outputs:

Output contacts:
SPCO 10Amps/250V AC1
DPCO 8Amps/250V AC1

Max breaking capacity:
SPCO 4000VA
DPCO 2000VA

Mechanical life: 30 Million ops

Electrical life: 200K ops at max rated load

General:

Operating temperature: -20°C to +65°C

Storage temperature: -20°C to +65°C

Max cable size: 4mm

CE marked: Yes

In accordance with:
EN61000-6-1: 2007
EN61000-6-3: 2007
EN61010-1: 2002

Housing material: Polycarbonate, Auto extinguishable to UL 94 V-0

TYPE

YWRUP (Din rail SPCO)
YWRUP (Din rail SPCO)
11WRUP (11 pin SPCO)
YWR2UP (Din rail DPCO)

SEQUENCE

*S

TIME DELAY

**T 0.1-10sec
**T 0.2-20sec
**T 0.3-30sec

VOLTAGE

3 x 110V
3 x 220V
3 x 380V
3 x 400V
3x 415V
3 x 440V***
SPECIAL****

SYSTEM

3W (3 wire)
4W (4 wire)

OPTION

On 3 wire variants as a no cost option a separate AC auxiliary supply can be specified 24VAC, 48VAC, 110VAC. This gives the possibility of additional “control circuit” voltage monitoring. If this is lost or is not present, the unit will de-energise or not energise as applicable.

* Insert S if sequence is required

** Insert Txxx if an adjustable time delay is required (din rail versions only)

*** 440V only available as a 3 wire version

**** Available on request special high voltage versions i.e 690V L-L. (Separate auxiliary supply required).

YWRUP-Connections.png#asset:3266

Dimensions-YW-8W11W.png#asset:3263